ic audio logo

DA-P 10-260/T-EN54

DA-P 10-260/T-EN54

DA-P 10-260/T-EN54
  • quick mounting
  • high impact ABS plastic
  • PG7 cable gland

EN 54-24:2008
Ref. Nr.: 020-17
ID-Code: SAA-LS20
1438-CPR-0388

ic audio GmbH, Boehringerstraße 14a,
D-68307 Mannheim, Germany

CE-Symbol gemäß Richtlinie 93/68EWG

The 10W-powered bi-directional speaker is equipped with two 130mm full-range loudspeakers and a 100V line transformer with 3 power adjustments. A robust ABS plastic housing in RAL 9016 and a solid aluminium mounting bracket ensure the permanent installation of this speaker.

For additional reliability, a ceramic block and a thermal fuse are provided in a junction box and the speaker chassis is impregnated against wetness.

The speaker is compliant with the British Standard BS 5839, Part 8.

ic audio logo

DA-P 10-260/T-EN54

Technical Data (Electrical)

Description DA-P 10-260/T-EN54
Power 10/5/2,5 W
Impedance (100V) 1000/2000/4000 ohm
Frequency Range 100 - 20.000 Hz
Frequency Response 90 - 25.000 Hz
SPL IEC268-5, 1W/1m 85,0 dB
SPL EN54-24, Pmax/4m 82,5 dB
Sensitivity EN54-24, 1W/4m 73,0 dB
Sensitivity EN54-24, 1W/1m 85,6 dB
Dispersion -6dB, 500Hz h / v 2x130° / 2x130°
Dispersion -6dB, 1KHz h / v 2x170° / 2x170°
Dispersion -6dB, 2KHz h / v 2x160° / 2x160°
Dispersion -6dB, 4KHz h / v 2x65° / 2x65°

Technical Data (Mechanical)

Dimensions 202 x 163 x 170 mm
IP Rating IP56
Weight (net) 1,82kg
Temperature range -25 / +70 C°
Mounting Mounting bracket
Connector ceramic block
Colour RAL 9016

Product Attributes

ic audio logo

DA-P 10-260/T-EN54

Technical Drawing

ic audio logo

DA-P 10-260/T-EN54

Frequency Response Diagram

Sensitivity
SPL Max
ic audio logo

DA-P 10-260/T-EN54

Isobar

ic audio logo

DA-P 10-260/T-EN54

Polar Diagram

DA-P 10-260/T-EN54
Polar Diagram 500Hz
DA-P 10-260/T-EN54
Polar Diagram 1000Hz
DA-P 10-260/T-EN54
Polar Diagram 2000Hz
DA-P 10-260/T-EN54
Polar Diagram 4000Hz
DA-P 10-260/T-EN54
Polar Diagram 8000Hz
ic audio logo

DA-P 10-260/T-EN54

ic audio loudspeakers are tested and classified according to the IEC standard 60529 (degree of protection by enclosure) against the penetration of foreign objects and moisture. The classification is conforming to standards through characterization with a fixed code. This code consists of the letters IP (International Protection) followed by two digits. The first digit indicates the degree of protection against dust and the second digit the degree of protection against water. Please note that the testing of the products has been carried out in laboratory conditions which are not always 100% comparable with the conditions of different installation environments. This protection can be reduced due to normal wear and tear depending on the installation environment.
RoHS compliant (2011/65/EU)
The IP rating specified is based on ic audio test results, not on CNBOP-PIB test results. Certification only verifies the minimum requirements for EN54-24 compliance.