ic audio logo

DL-P 10-165/T SWF-EN54

DL-P 10-165/T SWF-EN54

DL-P 10-165/T SWF-EN54 DL-P 10-165/T SWF-EN54
  • seawater proof
  • flat design
  • UV-resistant

EN 54-24:2008
Ref. Nr.: 04-19
ID-Code: SAA-LS11
1438-CPR-0718

ic audio GmbH, Boehringerstraße 14a,
D-68307 Mannheim, Germany

CE-Symbol gemäß Richtlinie 93/68EWG

The DL-P 10-165/T SWF-EN54 is ideally suited for indoor and outdoor use on ships. Thanks to its robust construction and high-quality materials, the ceiling speaker offers permanent protection against seawater and UV rays.

The 10W DL-P is equipped with a 165mm dual cone full-range speaker made of high-quality polypropylene for powerful sound reinforcement. The flat design ABS plastic housing offers a seawater-resistant cover for the terminal. Lateral ventilation slots provide optimal frequency response.

Thanks to the PG9 cable entry on the side, a space-saving connection is effortlessly possible.

The spring snap system reduces the installation time, and protective caps at the spring ends reduce possible vibrations to a minimum. Besides the classical maritime application, the DL-P with EN54-24 certification is also suited for voice alarm installations in swimming pools and similar wet areas.

Thanks to its special protective properties, this loudspeaker is also suitable for clean room applications according to ISO 14644-1.

This speaker is suitable for a ceiling strength of about 1-45 mm. Our specification is primarily related to solid ceilings, for ceilings with soft materials higher ceiling thicknesses could be necessary. In addition, stronger cables and other fittings may also result in changes in the appropriate setup. Regarding the variety of materials and manufacturers, we recommend building a sample of the speaker to match the requirements accurately.

ic audio logo

DL-P 10-165/T SWF-EN54

Technical Data (Electrical)

Description DL-P 10-165/T SWF-EN54
Power 10/6/3/1,5 W
Impedance (100V) 1000/1667/3333/6667 ohm
Frequency Range 50 - 24.000 Hz
Frequency Response 42 - 25.000 Hz
SPL IEC268-5, 1W/1m 88,8 dB
SPL EN54-24, Pmax/4m 86,2 dB
Sensitivity EN54-24, 1W/4m 78,9 dB
Dispersion -6dB, 500Hz 165°
Dispersion -6dB, 1KHz 165°
Dispersion -6dB, 2KHz 145°
Dispersion -6dB, 4KHz 65°
Please note: Because of many different types of ceiling materials and ceiling strengths we recommend to build in a sample of the speaker to match the requirements accurately.

Technical Data (Mechanical)

Dimensions 220x82 mm
IP Rating IP54
Weight (net) 1,20 kg
Ceiling Cut-out 175 mm
Temperature range -25 / +70 C°
Mounting Quick fit mounting
Connector 5-pin terminal
Terminal diameter 3,2 mm
Maximum cable passage 8 mm²
Colour RAL 9016

Product Attributes

ic audio logo

DL-P 10-165/T SWF-EN54

Technical Drawing

ic audio logo

DL-P 10-165/T SWF-EN54

Frequency Response Diagram

Sensitivity
SPL Max
ic audio logo

DL-P 10-165/T SWF-EN54

Isobar

ic audio logo

DL-P 10-165/T SWF-EN54

Polar Diagram

DL-P 10-165/T SWF-EN54
Polar Diagram 500Hz
DL-P 10-165/T SWF-EN54
Polar Diagram 1000Hz
DL-P 10-165/T SWF-EN54
Polar Diagram 2000Hz
DL-P 10-165/T SWF-EN54
Polar Diagram 4000Hz
DL-P 10-165/T SWF-EN54
Polar Diagram 8000Hz
ic audio logo

DL-P 10-165/T SWF-EN54

ic audio loudspeakers are tested and classified according to the IEC standard 60529 (degree of protection by enclosure) against the penetration of foreign objects and moisture. The classification is conforming to standards through characterization with a fixed code. This code consists of the letters IP (International Protection) followed by two digits. The first digit indicates the degree of protection against dust and the second digit the degree of protection against water. Please note that the testing of the products has been carried out in laboratory conditions which are not always 100% comparable with the conditions of different installation environments. This protection can be reduced due to normal wear and tear depending on the installation environment.
RoHS compliant (2011/65/EU)
The IP rating specified is based on ic audio test results, not on CNBOP-PIB test results. Certification only verifies the minimum requirements for EN54-24 compliance.