EN54
WA-AB 06-100/T-EN54
barcode 4 260590 180551

Wall speaker for Voice Alarm, A/B-cabling, 2x6W power, certified EN 54-24

Technical Data
Colour white
Dimensions 252x194x82 mm
Dispersion -6dB, 500Hz single h/v 175° double h/v 180°
Dispersion -6dB, 1KHz single h/v 180°/160° double h/v 145°/130°
Dispersion -6dB, 2KHz single h/v 150°/135° double h/v 90°/80°
Dispersion -6dB, 4KHz single h/v 105°/90° double h/v 50°/40°
Sensitivity EN54-24, 1W/1m 91,6 dB
Sensitivity EN54-24, 1W/4m 79,6 dB
Frequency Range 227 - 14.600 Hz (single) 224 - 14.300 Hz (double)
Frequency Response 165 - 23.500 Hz (single) 162 - 23.500 Hz (double)
SPL IEC268-5, 1W/1m 91,0 dB
SPL EN54-24, Pmax/4m 85,0 dB (single) 88,0 dB (double)
Power 2x 6/3/1,5 W
EN54
WA-AB 06-100/T-EN54
barcode 4 260590 180551
Mounting Instruction
  1. Guide the connection cables through the cut-out in the rear panel of the speaker.
  2. Attach the back panel of the speaker to the wall. Use the enclosed screws.
  3. Connect the cable to the 100V transformer.
  4. Place the loudspeaker housing on one side of the rear wall so that the clamping spring engages in the hole. Press the second clamping spring inwards with a screwdriver and at the same time press the speaker against the wall so that the second clamping spring engages
  5. Use the enclosed plastic caps to cover the side holes.

Please note: To avoid damage, we recommend loosening the cable lug with a flat-blade screwdriver when changing the cable to a different power tapping.

Cable lug