EN54
DL-E 06-130/T-EN54
barcode 4 260590 180155

Ceiling speaker for Voice Alarm, power 6W, certified EN 54-24

Technical Data
Colour RAL 9016
Dimensions 181,5x65 mm (plastic)
181,5x91,5 mm (metal)
Ceiling Cut-out 156 mm
Dispersion -6dB, 500Hz plastic/metal 180°
Dispersion -6dB, 1KHz plastic/metal 180°
Dispersion -6dB, 2KHz plastic/metal 140°
Dispersion -6dB, 4KHz plastic/metal 85°/84°
Sensitivity EN54-24, 1W/1m 86,8 dB
Sensitivity EN54-24, 1W/4m 74,8 dB (plastic)
74,2 dB (metal)
Frequency Range 104 - 17.200 Hz
Frequency Response 57 - 24.000 Hz
SPL IEC268-5, 1W/1m 87,0 dB (plastic) 86,0 dB (metal)
SPL EN54-24, Pmax/4m 85,0 dB
Power 6/3/1,5 W
EN54
DL-E 06-130/T-EN54
barcode 4 260590 180155
Mounting Instruction
  1. Create the necessary ceiling cut-out and check the installation depth.
  2. Loosen the nut in the middle of the rear touch guard.
  3. Remove the touch guard of the speaker.
  4. Connect the loudspeaker cable to the terminals 100V and COM.
    If necessary, select a different power tapping.
  5. Put the touch guard back on the loudspeaker and secure it with the nut.
  6. Fold up the clamping spring and insert the loudspeaker into the ceiling cut-out.
  7. Press the speaker into the ceiling until it is flush with the ceiling cut-out.

Mounting instruction with fire dome FE 130-EN54:

  1. Loosen the nuts and remove the fire dome.
  2. Guide the incoming cable through the cable gland of the fire dome.
  3. Connect the incoming line to the terminal of the loudspeaker.
  4. Replace the fire dome back on the speaker and fasten it with the nut.
  5. Fold up the clamping spring and insert the loudspeaker into the ceiling cut-out.
  6. Press the speaker into the ceiling until it is flush with the ceiling cut-out.
Power Tappings
black red white green
COM 6 3 1,5