EN54
DL 06-77/T-EN54
barcode 4 260590 180148

Ceiling speaker for Voice Alarm, power 6W, certified EN 54-24

Technical Data
Colour RAL 9016
Dimensions 104x100,5 mm
Ceiling Cut-out 86 mm
Dispersion -6dB, 500Hz h/v 180°
Dispersion -6dB, 1KHz h/v 180°
Dispersion -6dB, 2KHz h/v 180°
Dispersion -6dB, 4KHz h/v 81°
Sensitivity EN54-24, 1W/1m 80,4 dB
Sensitivity EN54-24, 1W/4m 68,4 dB
Frequency Range 98 - 20.000 Hz
Frequency Response 93 - 20.100 Hz
SPL IEC268-5, 1W/1m 80,0 dB
SPL EN54-24, Pmax/4m 79,0 dB
Power 6/3/1,5 W
EN54
DL 06-77/T-EN54
barcode 4 260590 180148
Mounting Instruction
  1. Create the necessary ceiling cut-out and check the installation depth.
  2. Insert the speaker cable through the cable entry of the connector housing.
  3. Connect the loudspeaker cable to the 100V and COM terminals.
    If necessary, select a different power tapping.
  4. Carefully close the connector housing again.
  5. Tension the springs upwards and insert the loudspeaker with the springs first into the ceiling cut-out.
  6. Carefully relieve the tension on the springs until the speaker is centred in the ceiling cut-out.