EN54
DL 06-165/T-EN54 STR
barcode 4 260590 181244

Ceiling speaker for Voice Alarm, 6W power, certified EN 54-24

Technical Data
Colour RAL 9010
Dimensions 220x109 mm
Ceiling Cut-out 198 mm
Dispersion -6dB, 500Hz h/v 180°
Dispersion -6dB, 1KHz h/v 175°
Dispersion -6dB, 2KHz h/v 100°
Dispersion -6dB, 4KHz h/v 50°
Sensitivity EN54-24, 1W/4m 81,0 dB
Frequency Range 404 - 10.100 Hz
Frequency Response 80 - 24.000 Hz
SPL IEC268-5, 1W/1m 93,0 dB
SPL EN54-24, Pmax/4m 89,0 dB
Power 6/3/1,5 W
EN54
DL 06-165/T-EN54 STR
barcode 4 260590 181244
Mounting Instruction
  1. Create the necessary ceiling cut-out and check the installation depth.
  2. Fix the outer ring in the ceiling.
  3. Attach the fire dome to the ring in the ceiling.
  4. Lift the three springs on the spring slots on the ring, and turn them to the side. Guide the connection cable through the opening.
  5. Position the fire dome below the notches and then push it upwards. Turn the springs back into the spring slots (starting position).
  6. Connect the loudspeaker cable to the 100V and COM terminals.
    If necessary, select a different power tapping.
  7. Use the enclosed mounting hook to place the grille in the speaker ring and turn it clockwise.

Please note: Do not insert the hook into the grille more than 5mm from the outer ring to avoid damage. We recommend loosening the cable lug with a flat-blade screwdriver when changing the cable to a different power tapping.

Cable lug