EN54
WA 06-165/T Metal-EN54 STR
barcode 4 260590 181749

Wall speaker for Voice Alarm, 6W power, certified EN 54-24

Technical Data
Colour RAL 9010
Dimensions 252x192x82 mm
Dispersion -6dB, 500Hz h=180° v=180°
Dispersion -6dB, 1KHz h=160° v=160°
Dispersion -6dB, 2KHz h=120° v=120°
Dispersion -6dB, 4KHz h=76° v=76°
Sensitivity EN54-24, 1W/4m 82,0 dB
Frequency Range 170 - 18.500 Hz
Frequency Response 70 - 23.500 Hz
SPL IEC268-5, 1W/1m 94,0 dB
SPL EN54-24, Pmax/4m 90,0 dB
Power 6/3/1,5 W
EN54
WA 06-165/T Metal-EN54 STR
barcode 4 260590 181749
Mounting Instruction
  1. Attach the back panel of the speaker to the wall. Use the enclosed screws.
  2. Feed the connection cable through the cut-out in the rear wall of the speaker or use the inputs on the side or top/bottom by knocking out the pre-punched holes and fitting them with the enclosed rubber grommets.
  3. Connect the power cable to the ceramic terminal (COM and 100V). If necessary, select a different power tapping on the transformer.
  4. Connect the red/black plug-in cable of the transformer to the loudspeaker.
  5. Place the loudspeaker housing on the wall-mounted rear wall of the loudspeaker.
  6. Use the 3 enclosed screws incl. spring washers to fasten the loudspeaker.

Please note: To avoid damage, we recommend loosening the cable lug with a flat-blade screwdriver when changing the cable to a different power tapping.

Cable lug