EN54
DL-AB 06-200/T-EN54W
barcode 4 260590 181404

Ceiling speaker for Voice Alarm, A/B-cabling, power 2x6, certified EN 54-24

Technical Data
Colour RAL 9010
Dimensions 267x138 mm
Ceiling Cut-out 243 mm
Dispersion -6dB, 500Hz 180° (h) s/d 180° (v) s/d
Dispersion -6dB, 1KHz 160° (h) s/d 160° (v) s/d
Dispersion -6dB, 2KHz 120° (h) s/d 90° (v) s/d
Dispersion -6dB, 4KHz 65° (h) s/d 40° (v) s/d
Sensitivity EN54-24, 1W/4m 77,8 dB (single) 80,8 dB (double)
Frequency Range 162 - 18.600 Hz (single) 159 - 16.000 Hz (double)
Frequency Response 125 - 23.500 Hz (single) 120 - 23.500 Hz(double)
Power 2x6/3/1,5 W
EN54
DL-AB 06-200/T-EN54W
barcode 4 260590 181404
Mounting Instruction
  1. Fasten the speaker ring in the ceiling cut-out by carefully folding the mounting springs. The tensile force of the springs provides a stable hold.
  2. Insert the enclosed rubber grommets into the two holes at the back of the fire dome.
  3. Insert the 100V speaker cables through the grommets of the fire dome.
  4. Slide the springs of the fire dome inwards and to the side. Position the fire dome in the speaker ring and snap the springs into place
  5. Connect the cable with the WAGO terminals to 100V and COM according to the required power. Fix the cable by lowering the lever of the terminal.
  6. Insert the grille into the speaker ring and carefully turn the grille clockwise. Use the enclosed mounting hook for this purpose. Do not insert the hook into the grille more than 5mm from the outer ring to avoid damage. The openings of the bayonet catches should be in a straight line with the rivets on the inner side of the speaker ring.

Please note: To avoid damage, we recommend loosening the cable lug with a flat-blade screwdriver when changing the cable to a different power tapping.

Cable lug