Compass Safe Distance: 2.80 m (standard compass), 1.45 m (steering and emergency compass)
to prevent magnetic interference with navigational instruments
TS-C 06-140/T MED
4260590186362
Mounting Instruction
Mount the swivel bracket on the wall.
Fit the sound column on the swivel bracket.
Unscrew the base of the sound column.
Insert the incoming cable through the cable gland and connect it to the terminal.
Screw the base back onto the sound column.
To ensure uninterrupted operation of the public address and voice evacuation system
during a fault condition, this loudspeaker is equipped with integrated short-circuit protection:
A Ceramic Terminal Block ensures high-temperature resistance and electrical isolation of the input connection.
A Thermal Fuse automatically disconnects the loudspeaker driver in the event of excessive heat (e.g., due to fire or
driver failure), preventing a short circuit across the 100V line.
Do not bypass or remove the thermal fuse under any circumstances.
Ensure correct polarity when connecting to the ceramic terminal block.
Verify the integrity of protection components during periodic maintenance.